Address Setting via Coding Switch and iPar Server Functionality
- The system is in a safe state.
- Switch off the supply voltage of the fieldbus node containing the F I/O module to be replaced.
- Pull the F I/O module to be replaced out of the fieldbus node.
- Read the device address on the coding switch of the F I/O module to be replaced and apply this setting to the replacement module.
- Insert the replacement module into the fieldbus node at the position of the F I/O module to be replaced.
- Switch the power supply to the respective fieldbus node back on.
- After startup, the individual module parameters are automatically loaded from the iPar server into the F I/O module.
- The safety-related verification of these parameters takes place automatically in the F I/O module.
- If the process cannot be completed successfully, the replacement module remains in its initial state and must be parameterized using the WAGO Safety Editor 75x.
- The verification step is successful.
- The module is ready for operation.