Replacement without GSD Parameterization or iPar Server Functionality

  1. The system is in a safe state.
  1. Switch off the supply voltage of the fieldbus node containing the F I/O module to be replaced.
  2. Pull the F I/O module to be replaced out of the fieldbus node.
  3. Read the device address on the coding switch of the F I/O module to be replaced and apply this setting to the replacement module.
  4. If the set address is “0,” the device address of the F I/O module must be set with the WAGO Safety Editor 75x.
  5. Insert the replacement module into the fieldbus node at the position of the F I/O module to be replaced.
  6. Switch the power supply to the respective fieldbus node back on.
  7. Set the software address of the F I/O module using the WAGO Safety Editor 75x.
  8. Restart the fieldbus node.
  1. The module is ready for operation.