Replacement without GSD Parameterization or iPar Server Functionality
- The system is in a safe state.
- Switch off the supply voltage of the fieldbus node containing the F I/O module to be replaced.
- Pull the F I/O module to be replaced out of the fieldbus node.
- Read the device address on the coding switch of the F I/O module to be replaced and apply this setting to the replacement module.
- If the set address is “0,” the device address of the F I/O module must be set with the WAGO Safety Editor 75x.
- Insert the replacement module into the fieldbus node at the position of the F I/O module to be replaced.
- Switch the power supply to the respective fieldbus node back on.
- Set the software address of the F I/O module using the WAGO Safety Editor 75x.
- Restart the fieldbus node.
- The module is ready for operation.